Flanking Transmission Across Horizontal CLT Junctions; Measurements vs. Predictive Modeling

Loading...
Thumbnail Image

Date

Type

Examensarbete för masterexamen
Master's Thesis

Model builders

Journal Title

Journal ISSN

Volume Title

Publisher

Abstract

This thesis investigates vibration transmission across horizontal CLT junctions in a residential building at Sjöhusen in Klockelund. In situ measurements were carried out to determine the direction-averaged velocity level difference, Dv,ij, and, where applicable, the vibration reduction index, Kij, for selected building elements at three junctions including walls, a glulam beam, and two ceiling configurations. Transient excitation measurements were performed in accordance with ISO 10848-1. Measured Kij values for the ceilings and the glulam beam were compared with predictions from the estimation model in Annex E of ISO 12354-1 implemented in BASTIAN. Weighted sound reduction indices were calculated from both measured and predicted Dv,ij values. The wall extending into the stairwell exhibited low vibration reduction at mid frequencies, indicating significant flanking transmission. Excitation from the apart ment side yielded lower velocity-level differences than excitation from the stairwell, while the door opening altered the transmission relative to the continuous wall. For the ceiling structures, the glulam beam introduced spatial variation in measured Dv,ij values, but only a minor effect on the weighted sound reduction index, with R′ Ff,w(C50−3150) = 58(−2) dB and 59(−1) dB. The ISO 12354-1 model generally agreed with measurements but underestimated Kij at low frequencies. A discrepancy was also observed between predicted weighted sound reduction from measured Dv,ij values and results from ISO 12354-1 in BASTIAN, suggesting that the conversion from Kij to Dv,ij according to ISO 12354-1 contributes to this deviation. Beam-to-beam measurements indicated that the glulam beam itself exhibits good performance in terms of vibration transmission. However, due to rigid coupling with the adjacent ceiling elements, it forms an efficient flanking transmission path across the structurally separated floor systems. Overall, the results show that vibration transmission in CLT junctions is strongly influenced by structural configuration. This highlights the importance of consider ing junction design, in particular structural separation, at an early stage to avoid unintended flanking transmission paths.

Description

Keywords

vibration transmission, flanking transmission, cross-laminated timber (CLT), transient excitation, in-situ measurements, horizontal structural junctions, sound reduction index, ISO 10848, ISO 12354

Citation

Architect

Location

Type of building

Build Year

Model type

Scale

Material / technology

Index

Endorsement

Review

Supplemented By

Referenced By