Flanking Transmission Across Horizontal CLT Junctions; Measurements vs. Predictive Modeling
Loading...
Date
Authors
Type
Examensarbete för masterexamen
Master's Thesis
Master's Thesis
Programme
Model builders
Journal Title
Journal ISSN
Volume Title
Publisher
Abstract
This thesis investigates vibration transmission across horizontal CLT junctions in a
residential building at Sjöhusen in Klockelund. In situ measurements were carried
out to determine the direction-averaged velocity level difference, Dv,ij, and, where
applicable, the vibration reduction index, Kij, for selected building elements at three
junctions including walls, a glulam beam, and two ceiling configurations.
Transient excitation measurements were performed in accordance with ISO 10848-1.
Measured Kij values for the ceilings and the glulam beam were compared with
predictions from the estimation model in Annex E of ISO 12354-1 implemented in
BASTIAN. Weighted sound reduction indices were calculated from both measured
and predicted Dv,ij values.
The wall extending into the stairwell exhibited low vibration reduction at mid
frequencies, indicating significant flanking transmission. Excitation from the apart
ment side yielded lower velocity-level differences than excitation from the stairwell,
while the door opening altered the transmission relative to the continuous wall.
For the ceiling structures, the glulam beam introduced spatial variation in measured
Dv,ij values, but only a minor effect on the weighted sound reduction index, with
R′
Ff,w(C50−3150) = 58(−2) dB and 59(−1) dB. The ISO 12354-1 model generally
agreed with measurements but underestimated Kij at low frequencies. A discrepancy
was also observed between predicted weighted sound reduction from measured Dv,ij
values and results from ISO 12354-1 in BASTIAN, suggesting that the conversion
from Kij to Dv,ij according to ISO 12354-1 contributes to this deviation.
Beam-to-beam measurements indicated that the glulam beam itself exhibits good
performance in terms of vibration transmission. However, due to rigid coupling with
the adjacent ceiling elements, it forms an efficient flanking transmission path across
the structurally separated floor systems.
Overall, the results show that vibration transmission in CLT junctions is strongly
influenced by structural configuration. This highlights the importance of consider
ing junction design, in particular structural separation, at an early stage to avoid
unintended flanking transmission paths.
Description
Keywords
vibration transmission, flanking transmission, cross-laminated timber (CLT), transient excitation, in-situ measurements, horizontal structural junctions, sound reduction index, ISO 10848, ISO 12354